HEAT DISSIPATION
  

AUTOMATIC POWER FACTOR REGULATORS

 Type

Rated supply voltage Us
 
[V] 

Maximum dissipation at rated supply 
voltage Us
[W]  

   

DCRK5

380-415VAC

2.2

DCRK7

 380-415VAC

2.7

DCRK8

 380-415VAC

2.4

DCRK12

 380-415VAC

3.0

 

 

 

DCRJ8

 110-240VAC

5.0

DCRJ12

 110-240VAC

5.5

DCRJ12F

 110-240VAC

5.5

     
     
To calculate total heat dissipation, add contact dissipation to the value given above.   
The maximum specific dissipation of the relay contacts is 0.1W/A.   
The estimate of contact dissipation is to be made considering total contact current and the diversity factor if the device is equipped with more than one output relay.

          