HEAT DISSIPATION
  
 AUTOMATIC BATTERY CHARGERS

Type

Rated supply 
voltage Us


[V]

Maximum dissipation
at rated supply voltage Us
[W]

 

 

BCE 0312

220-240VAC

24

BCE 0612

220-240VAC

46

BCE 1212

220-240VAC

73

BCE 2V524

220-240VAC

26

BCE 0524

220-240VAC

40

BCE 1024

220-240VAC

66

   
To calculate total heat dissipation, add contact dissipation to the value given above.   
The maximum specific dissipation of the relay contacts is 0.2W/A.   
The estimate of contact dissipation is to be made considering total contact current and the diversity factor if the device is equipped with more than
one output relay.

    